Boiler Temperature
Units: °F °C
Index Name Units Boiler 1Boiler 2
Current Value Last Changed Prev. ValueCurrent ValueLast ChangedPrev. Value
481 Boiler temperature setpoint °C 74.0 2014-03-06 10:32:05 (GMT-5) 80.0 74.0 2014-03-06 10:37:25 (GMT-5) 80.0
1 Shutdown if current boiler temperature is higher than boiler setpoint + Δ°C 9.0 2014-03-06 10:32:05 (GMT-5) 5.0 9.0 2014-03-06 10:37:25 (GMT-5) 5.0
8 Maximum boiler setpoint °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 80.0 2013-12-27 10:28:22 (GMT-5) 80.0
9 Always switch off at maximum boiler setpoint + Δ°C 3.0 2014-03-06 10:32:05 (GMT-5) 5.0 3.0 2014-03-06 10:37:25 (GMT-5) 5.0
482 Minimum boiler temperature to release all pumps °C 50.0 2014-03-06 10:32:05 (GMT-5) 35.0 60.0 2014-03-06 10:37:25 (GMT-5) 35.0
514 Temperature in the hi-limit stat housing at which all pumps run °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 80.0 2013-12-27 10:28:22 (GMT-5) 80.0
811 Start emergency skimming from STL sensor temp. °C 102.0 2013-12-27 10:28:14 (GMT-5) 102.0 102.0 2013-12-27 10:28:22 (GMT-5) 102.0
75 Heating circuit overheat in variable mode Δ°C 2.0 2013-12-27 10:28:14 (GMT-5) 2.0 2.0 2014-01-10 08:48:11 (GMT-5) -