Boiler Temperature
Units: °F °C
Index Name Units Boiler 1Boiler 2
Current Value Last Changed Prev. ValueCurrent ValueLast ChangedPrev. Value
481 Boiler temperature setpoint °C 79.0 2015-10-14 14:09:41 (GMT-5) 76.0 79.0 2015-10-14 14:09:41 (GMT-5) 84.0
1 Shutdown if current boiler temperature is higher than boiler setpoint + Δ°C 6.0 2015-10-14 14:09:41 (GMT-5) 9.5 6.0 2015-10-14 14:09:41 (GMT-5) 2.0
8 Maximum boiler setpoint °C 82.0 2015-10-14 14:10:13 (GMT-5) 84.5 82.0 2015-10-14 14:10:13 (GMT-5) 84.5
9 Always switch off at maximum boiler setpoint + Δ°C 3.0 2015-10-14 14:10:13 (GMT-5) 0.5 3.0 2015-10-14 14:10:13 (GMT-5) 0.5
482 Minimum boiler temperature to release all pumps °C 35.0 2014-11-21 16:31:09 (GMT-5) 50.0 35.0 2014-11-21 16:40:43 (GMT-5) 50.0
514 Temperature in the hi-limit stat housing at which all pumps run °C 78.0 2013-11-22 09:54:12 (GMT-5) 80.0 78.0 2013-11-22 10:27:28 (GMT-5) 80.0
811 Start emergency skimming from STL sensor temp. °C 102.0 2013-10-26 01:26:04 (GMT-5) 102.0 102.0 2013-10-26 01:26:12 (GMT-5) 102.0
75 Heating circuit overheat in variable mode Δ°C 2.0 2013-11-21 10:00:13 (GMT-5) - - 2014-01-16 14:41:27 (GMT-5) 2.0