Boiler Temperature
Units: °F °C
Index Name Units Boiler 1Boiler 2Boiler 3
Current Value Last Changed Prev. ValueCurrent ValueLast ChangedPrev. ValueCurrent ValueLast ChangedPrev. Value
481 Boiler temperature setpoint °C 82.0 2020-12-08 10:35:54 (GMT-5) 85.0 82.0 2020-12-08 10:35:54 (GMT-5) 85.0 82.0 2020-12-08 10:35:54 (GMT-5) 85.0
1 Shutdown if current boiler temperature is higher than boiler setpoint + Δ°C 8.0 2015-10-13 14:10:49 (GMT-5) 4.0 8.0 2015-10-13 13:57:04 (GMT-5) 3.0 8.0 2015-10-13 14:10:49 (GMT-5) 5.0
8 Maximum boiler setpoint °C 90.0 2015-10-13 14:00:29 (GMT-5) 88.0 90.0 2015-10-13 14:00:29 (GMT-5) 88.0 88.0 2020-12-14 08:18:28 (GMT-5) 90.0
9 Always switch off at maximum boiler setpoint + Δ°C 3.0 2014-08-29 17:15:06 (GMT-5) 3.0 3.0 2014-08-29 17:15:09 (GMT-5) 3.0 3.0 2014-08-29 17:15:12 (GMT-5) 3.0
482 Minimum boiler temperature to release all pumps °C 35.0 2014-08-29 17:15:07 (GMT-5) 35.0 35.0 2014-08-29 17:15:10 (GMT-5) 35.0 35.0 2014-08-29 17:15:13 (GMT-5) 35.0
514 Temperature in the hi-limit stat housing at which all pumps run °C 80.0 2014-08-29 17:15:07 (GMT-5) 80.0 80.0 2014-08-29 17:15:10 (GMT-5) 80.0 80.0 2014-08-29 17:15:13 (GMT-5) 80.0
811 Start emergency skimming from STL sensor temp. °C 102.0 2014-08-29 17:15:08 (GMT-5) 102.0 102.0 2014-08-29 17:15:11 (GMT-5) 102.0 102.0 2014-08-29 17:15:14 (GMT-5) 102.0
75 Heating circuit overheat in variable mode Δ°C 2.0 2014-08-29 17:15:06 (GMT-5) 2.0 2.0 2014-08-29 17:15:09 (GMT-5) 2.0 2.0 2014-08-29 17:15:12 (GMT-5) 2.0