Cascade System
Units: °F °C
Index Name Units Boiler 1Boiler 2
Current Value Last Changed Prev. ValueCurrent ValueLast ChangedPrev. Value
226 Store charge 1 1 1 % 80 2021-09-14 08:28:55 (GMT-5) 81 0 2013-12-27 10:28:10 (GMT-5) 0
842 Buffer charge is 100 % at boiler setpoint parameter Δ°C -6.0 2014-03-06 10:32:05 (GMT-5) 3.0 4.0 2013-12-27 10:28:22 (GMT-5) 4.0
843 Store charge is 0 % at the following temperature °C 40.0 2014-03-06 10:32:05 (GMT-5) 58.0 30.0 2013-12-27 10:28:22 (GMT-5) 30.0
844 Start of store charging from charge % 86 2014-03-06 10:33:09 (GMT-5) 87 75 2013-12-27 10:28:22 (GMT-5) 75
845 Start point 2 at store charge % 70 2014-03-06 10:33:09 (GMT-5) 65 60 2013-12-27 10:28:22 (GMT-5) 60
846 Start point 3 at store charge % 40 2013-12-27 10:28:14 (GMT-5) 40 40 2013-12-27 10:28:22 (GMT-5) 40
852 Quick start if store discharge is greater than (% / 10min) 40 2014-03-06 10:33:09 (GMT-5) 20 15 2013-12-27 10:28:22 (GMT-5) 15
853 Reduce the overall output of the cascade before the store is fully loaded % 0 2014-01-24 10:00:57 (GMT-5) 60 0 2013-12-27 10:28:22 (GMT-5) 0
847 Start priority of the master boiler 1 2013-12-27 10:28:14 (GMT-5) 1 1 2013-12-27 10:28:22 (GMT-5) 1
848 Start priority of slave boiler 1 1 2013-12-27 10:28:14 (GMT-5) 1 2 2013-12-27 10:28:22 (GMT-5) 2
849 Start priority of slave boiler 2 3 2013-12-27 10:28:14 (GMT-5) 3 3 2013-12-27 10:28:22 (GMT-5) 3
850 Start priority of slave boiler 3 4 2013-12-27 10:28:14 (GMT-5) 4 4 2013-12-27 10:28:22 (GMT-5) 4